AHU system overview

All AHU rooms

--:--

 

 

AHU9

Running

6

Standby

1

Disable

1

Alarm

1

Running16.0hr

Dip Line LAHU-01

Efficiency84.0%

Power

883 kWh

Airflow

14,000 CMH

Running16.0hr

Dip Line RAHU-02

Efficiency83.0%

Power

631 kWh

Airflow

10,500 CMH

Running16.0hr

Former WashAHU-03

Efficiency82.0%

Power

505 kWh

Airflow

8,500 CMH

Alarm16.0hr

StrippingAHU-04

Efficiency80.0%

Power

303 kWh

Airflow

5,800 CMH

Running16.0hr

QC LabAHU-05

Efficiency79.5%

Power

201 kWh

Airflow

3,700 CMH

Running16.0hr

DSP PackingAHU-06

Efficiency89.0%

Power

476 kWh

Airflow

7,200 CMH

Standby0.0hr

WarehouseAHU-07

Efficiency—%

Power

29 kWh

Airflow

0 CMH

Disable0.0hr

OfficeAHU-08

Efficiency—%

Power

0 kWh

Airflow

0 CMH

Running16.0hr

CanteenAHU-09

Efficiency85.0%

Power

381 kWh

Airflow

6,400 CMH

AI recommendations

Updated 09:00
79
HEALTH

AHU fleet needs attention

2 pts

6/9 AHUs normal at 83.7% avg. efficiency. 1 alarm and 2 saving opportunities need attention.

AHU-04 filter pressure drop highFilter ΔP 285 Pa vs 250 Pa limit · replace the filter nowNOWAHU-01 chilled water valve at 96%Supply air 1.2 °C above set point · check CHW supply temp< 4HReset duct static pressure450 → 400 Pa on AHU-01–03 · save ≈ ฿1,100 / daySAVE 8%
ASK AI · 09:02

Why is AHU-04 in alarm?

Filter ΔP climbed 190 → 285 Pa over 9 days, so the fan works harder for less air (5,800 CMH vs 6,500 design). Replace the bag filter on AHU-04.

AHU-04 · Filter ΔPAirflow history

Energy consumption trend

  • Today (kWh)
  • Yesterday (kWh)