Chiller room B-12
Chiller6
Running
3
Standby
1
Disable
1
Alarm
1
500 TRCH-01
Power
5,974 kWh
BTU
25,896 kWh
Water Inlet (PIT)
3.6 bar
Water Outlet (PIT)
3.1 bar
500 TRCH-02
Power
4,093 kWh
BTU
17,733 kWh
Water Inlet (PIT)
3.5 bar
Water Outlet (PIT)
3.0 bar
500 TRCH-03
Power
1,069 kWh
BTU
4,273 kWh
Water Inlet (PIT)
2.2 bar
Water Outlet (PIT)
2.2 bar
400 TRCH-04
Power
4,244 kWh
BTU
16,169 kWh
Water Inlet (PIT)
3.7 bar
Water Outlet (PIT)
3.0 bar
400 TRCH-05
Power
2,680 kWh
BTU
12,260 kWh
Water Inlet (PIT)
3.4 bar
Water Outlet (PIT)
2.9 bar
400 TRCH-06
Power
0 kWh
BTU
0 kWh
Water Inlet (PIT)
— bar
Water Outlet (PIT)
— bar
Chiller room needs attention
3/6 chillers normal at 0.81 kW/TR. 1 alarm and 2 saving opportunities need attention.
Condenser approach rose 1.6 → 4.8 K over 12 days while CW flow stayed flat — the tubes are fouling. CH-04 now runs at 0.91 kW/TR; schedule a tube brush and check the water treatment.