Chiller system overview

AI recommendations

Updated 09:00
80
HEALTH

Chiller room needs attention

2 pts

3/6 chillers normal at 0.81 kW/TR. 1 alarm and 2 saving opportunities need attention.

CH-04 condenser approach high4.8 K vs 2.0 K limit · 0.91 kW/TR · clean condenser tubesNOWCH-02 low chilled water ΔTΔT 3.9 °C vs 5.5 °C design · check AHU valves on the loop< 4HRaise CHW set point 7 → 8 °COff-peak 22:00–06:00 · save ≈ ฿2,600 / daySAVE 4%
ASK AI · 09:02

Why is CH-04 in alarm?

Condenser approach rose 1.6 → 4.8 K over 12 days while CW flow stayed flat — the tubes are fouling. CH-04 now runs at 0.91 kW/TR; schedule a tube brush and check the water treatment.

CH-04 · Condenser approachkW/TR history

Energy consumption trend

  • Power (kWh)
  • BTU (kWh)