Floor B · All systems
Floor B · 58 zones · 312 devices
Drag to rotate · Scroll to zoom · Click a room for details
Scope 1
15K
Scope 2
9K
Scope 3
20K
Plant needs attention
A high fire risk in Electrical room B-11A and three plant alarms — BOILER-004 pressure, CH-04's fouled condenser and AHU-04's clogged filter — need attention; the afternoon peak can be shaved by pre-cooling.
Electrical room B-11A: 52.4 °C and rising about 3 °C every 10 minutes, tracking the DB-B11A panel load (92 %). Send someone to check the panel and its ventilation now. Next is BOILER-004 at 10.8 bar against a 10.0 bar limit — switch it to standby and check the safety valve. CH-04's condenser approach is 4.8 K, so move its load to CH-03 until the tubes are cleaned.
10.9 bar max
BOILER-004 over limit · 4 units
Run 1 · Stby 1 · Off 1 · Alarm 1
Open dashboard1,064 kW
COP 4.33 · 6 units
Run 3 · Stby 1 · Off 1 · Alarm 1
Open dashboard7 / 9 running
Avg. eff. 84 % · 4 rooms
Run 6 · Stby 1 · Off 1 · Alarm 1
Open dashboard52.4 °C max
186 / 190 sensors · AI risk High
Normal 184 · Offline 4 · Alarm 2
Open dashboard1,974 kW
27.0 MWh today
Chiller · AHU · Boiler · Others
Open dashboard